PUMPFIX BASIC SMARTCONTROL DN32
Pump set for mixing heating circuit with regulator Smartcontrol.

Components:
  • ball valve with thermometer (0 – 120°C) and check valve - BLUE
  • ball valve with thermometer (0 – 120°C) - RED
  • circulation pump
  • welded steel spacer (black)
  • 3 way mixing valve
  • insulating shell
  • connection G3/4” for installation of overflow valve
  • regulator Smartcontrol
Category:
  • QUALITY
  • USAGE
  • TECHNICAL DATA
  • INSTALLATION
  • DOCUMENTATION
  • DIMENSIONS
The HERZ- PUMPFIX SMARTCONTROL pump group is used in heating and cooling systems in households. It allows for the installation of circulation pumps from various manufacturers and types. The integrated 3-way valve is used to regulate temperature in combination with the Smartcontrol smart controller. The Smartcontrol regulates the operation of the 3-way valve and the pump trough temperature sensors, ensuring always optimal settings.

T1 – temperature sensor for hot water circuit
T2 – temperature sensor for the heat source

T1 (included in set)
The temperature sensor T1 is located in the ball valve on the hot water system. It measures the temperature of the hot water after the circulation pump.
t1

T2 (included in set)
The temperature sensor T3 is inserted at the location of the heat source and measures the temperature of the heat source. The cable length is 3 meters.
Heat source can be:
  • BUFFER
  • BOILER


SCHUKO PLUG (included in set)
The HERZ Smartcontrol motorized smart controller is equipped with a Schuko connector, making the entire system "Plug & Play." Thanks to the Schuko plug, the smart controller can be easily connected to standard European electrical outlets, ensuring a quick and hasslefree installation process. This feature significantly simplifies the setup, as no complex wiring or additional components are required.
Nominal pressure: max. 10 bar
Max. operating temperature: 110 °C
Short-term load: 120 °C < 15 s
Min. operating temperature 0 °C (voda 0,5 °C)
Opening pressure for check valve: 200 mmWc
Propylene glycol mixing ratio: 25-50%

Heating water according to ÖNORM H5195 or VDI- Standard 2035. The use of ethylene, or propylene glycol in a mixing ratio of 25- 50% is allowed. EPDM gaskets can be affected by Mineral oils lubricants and thus lead to failure of the EPDM seals. Please refer to the manufacturers documentation when using ethylene glycol products for frost and corrosion protection.

COmponents

Components:
1. Valve with thermometer (blue) and non-return valve
2. Valve with thermometer (red)
3. Spacer
4. Circulation pump*
5. Three way valve with a actuator (1778160)
ART. IDENT DN PN EAN CIRCULATION PUMP KVS L[MM] H[MM] L1[MM] L2[MM] L3[MM]  L4[MM]  L5[MM] L6[MM]  G*[IN] G1**[IN]
PF 3210BSC 1751570 32 10 3838963244622 - 10 250 430 209 125 68 16 12 180 1-1/4 1-1/2
PF 3211BSC  1751571 32 10 3838963244639 - 16 250 430 209 125 68 16 12 180 1-1/4 1-1/2
PF 3212BSC  1751572 32 10 3838963244646 WILO PARA 30-180/6-43/SC -12 10 250 430 209 125 68 16 12 180 1-1/4 1-1/2
PF 3213BSC  1751573 32 10 3838963244653 WILO PARA 30-180/6-43/SC -12 16 250 430 209 125 68 16 12 180 1-1/4 1-1/2